The high-performance compact customer substation.
The substation consists of two monolithic prefabricated concrete sections. The sections, consisting of the base tray, midsection and roof, are expertly assembled in the factory.
The exterior surface of the midsection can be finished according to the customer’s wishes. The following options are available: exposed aggregate concrete, quartz gravel, fair-faced concrete, float finish or roll-on stucco with RAL finish coat, brick tile facing, and Dupa stone.
The substation is equipped with dual double-skin hot-dip galvanised steel doors without ventilation. The doors have a four-point locking system with a lock ready for fitting a profile cylinder, or two profile cylinders on request.
VERSATILE, COMPACT LOCAL GRID AND CUSTOMER SUBSTATIONS
- Manufactured in accordance with IEC 62271-202 (VDE 0670-202)
- Suitable for fitting out with transformers up to 1000/2000 kVÄ
- Arc tested with various SF6-insulated MV switchgear, including ABB Safe-Ring / Safe Plus, Ormazabal GAE, Schneider RM6 and Siemens 8DJH
- Arc tested with various air-insulated MV metering panels, including Elley MF10/20 and Ormazabal GAE-1Mx
- Manufactured in accordance with the 26th German Federal Immission Control Ordinance (BimSchV)
- Supplied with a full complement of electrical equipment, ready for connection
1. SUBSTATION DESCRIPTION
The GBÜ 1000/2000 Compact Substation is a space-saving, general-purpose local grid and customer substation with a wide range of configuration options. It is designed for use in the power range up to 1000/2000 kVA. The substation is manufactured in compliance with the relevant regulations such as IEC , DIN, VDE and UVV, as well as the following standards in particular:
- IEC 62271-202 (VDE 0671-202)
- DIN 1045:2008-08
- 26th BimSchV (26th German Federal Immission Control Ordinance)
- WHG (German Water Resources Act)
2. CONSTRUCTION
The substation consists of two monolithic prefabricated concrete sections (body and roof). The MV cables are fed in using watertight entry systems (e.g. Hauff). The LV cable can be brought in through a cable entry duct open at the bottom. An LV cable entry with a watertight entry system is available as an option. The surface finish of the substation can be individually customised to suit customer wishes. Exposed aggregate concrete, fair-faced concrete, float-finish and roll-on stucco with a choice of colours from the RAL colour card,
brick tile facing and other special finishes are available.̈
3. DOORS AND VENTILATION
All substation doors and ventilation components made by us can be manufactured from either galvanised steel or aluminium, depending on the customer’s choice. The doors are equipped with door stops, copper earthing straps and swivel lever locks for either one or two profile cylinders. Two-point locking systems for each door leaf eliminate arcing risk with the doors closed. The ventilation grilles are pick-proof and can optionally be fitted with insect screens.
4. ELECTRICAL CONFIGURATION
The electrical configuration of the substation with medium-voltage switchgear, transformer, low-voltage distribution panel, MV and LV cables, earthing, etc. is carried out at the factory according to customer specifications in compliance with IEC 62271-202.
5. TRANSPORT / INSTALLATION
The substation is delivered by truck to the job site as a complete unit ready for connection and is set down in the foundation pit prepared for it with the aid of a truck-mounted or mobile crane. Four lifting points in the base are provided for lifting the substation.
Other pictures
Section & Ground Plans
Technical Data
Ground Level:
approx. 1.900 mm
Components
Lmax = 2200 mm
Wmax = 1050 mm
Hmax = 2200 mm
Wmax = 2100 mm
Hmax = 1600 mm
Dmax = 850 mm
Wmax = 2100 mm
Hmax = 1600 mm
Dmax = 300 mm
Lmax = 2200 mm
Wmax = 1400 mm
Hmax = 2200 mm
(1) A 2,500 kVA version of the substation is available on request.
Wmax = 2100 mm
Hmax = 1600 mm
Dmax = 850 mm
Wmax = 2100 mm
Hmax = 1600 mm
Dmax = 400 mm